Adjustment item to the value of £1. Useful if adding items to the order...
Brand new 12v 7AH cell, perfect for rebuilding UPS battery banks.These...
Tags
af401a-reset
Refurbished
HP af401a nic - used- working
Reset to manufacturers defaults
Warning: Last items in stock!
Availability date:
We reset these cards to manufacturer default and then set either your nominated IP address or if you dont give us one an address that we can test with our network. We let you know the IP address the card is set to. You can then configure (and change the address) using the management interface.
Username: admin
Password: admin
If your UPS has the right shaped slot this card will most likely work - feel free to email us to confirm. We have used with the below UPS.
R3000XR
R1500XR
T1500XR
T2200XR
T1000XR
R12000XR /3 /1
Strange pin out for the config cable.
Female DB9 one end and RJ47 on the other.
DB9 pin order is top when the top row has 5 pins from 1 to 5 STARTING ON THE RIGHT
RJ45 pin order is when holding 'upside down' with the retaining tab below, and looking at the copper contactors, Pin one on the left.
DB9 Pin Goes to RJ45
1 - 7
2 - 5
3 - 4
4 - 2 and 3 (correct)
5 - 6
6 - 7
7 - 8
8 - 1
9 - no connection
notes Dsub 4 goes to two RJ45 pins (2 & 3)
Dsub pins 1 and 6 both go to RJ45 pin 7
I hope someone leaves a funny review in thanks for this pin out. I dont think it exists anywhere else on the internet.